Dual Output 1 Phase AC Voltage Transducer (FPVT)

Modell nr.
FPVT

Anpassad
Anpassad

Manufacturers
Haiyan Jinhan Electronic Technology Co.,Ltd

Export Markets
Global

Production Process
Integration

Shell Material
Iron-Shell

Freight
by Air

Leveranstid
1 Vecka

N.W
About 1kg

Dimension
112*133*93.5

Installation
Screws

MOQ
1 Piece

Transportpaket
Independent Carton Package

Specifikation
SGS

Varumärke
JINHAN

Ursprung
Zhejiang, Kina

HS-kod
9030390000

Produktionskapacitet
1000 st/år

Beskrivning

Technical Specification

Reference Standard
GB/T 13850-1998(IEC688-1992)
Accuracy
Long Term stability ≤±0.2%/year.No accumulation error
Temperature influence ≤ 100ppm/oC
Response Time
<400ms
Output Ripple <0&period;4&percnt;&lpar;peak-peak value&rpar;
Input burden Current less 0&period;2VA&semi;voltage less 0&period;1VA
Frequency Nominal frequency &pm;10&percnt;
Maximum output load Current output Max10V pressure drop
Auxiliary power Ratedvoltage80&percnt;-120&percnt;&comma;rated current 90&percnt;-110&percnt;
Auxiliary load effect
<&pm; 0&period;1&percnt;
Allow excessive input Current 3rate continuous 10rate 30 secs voltageMax 2ratecontinuous
Dielectric strength Input &sol;output &sol;power&sol;between the crust 2KV AC 1 minIEC866
Impact test ANSIC37&period;90a&sol;1973&comma;IEC255-4 &lpar;5kV1&period;2&sol;50us PulsedVoltage&rpar;
Calibration amplitude Full scale least&pm;3&percnt;&comma;zero least&pm;1&percnt;
Magnetic field effect 0&period;4KA&sol;m magnetic field strength change <0&period;05&percnt;
Operating condition Temperature -10~55oC relative humidity≤95&percnt;RHnoncondensing
Storage condition Temperature -40~70oC relative humidity ≤95&percnt; RHnoncondensing



Main functions and Characteristics
Transforms the measured signal to a voltage&comma; after HCNR200 linearity photodiode transforms to DC output which has extremely good linear relations with the measured signal&comma; uses the computer aided designed&comma; the principle is simply&comma; circuitry designed concisely&comma; reliability is highly and installment is conveniently&period;
Notice
Operating environment should not have the electric dust and gas of corrosive metal and destruction insulation existence&comma; the altitude should less than 2&comma;500 meters&period;
The Zero and CAL have been adjusted when products left factory&period; Please don’t adjust at will&period;