説明

A-C2 series dismountable hall effect current Transmitter is an open loop device based on the measuring principle of the hall effect, with a galvanic isolation between primary and secondary circuit. It provides accurate electronic measurement of AC or pulsed currents.
| Electrical data (Ta=25ºC±5℃) |
| タイプ | A-C2- 50あ |
A-C2- 100あ |
A-C2- 200あ |
A-C2- 300あ |
A-C2- 400あ |
A-C2- 500あ |
Unit |
| Rated current(Ipn AC) | 50 | 100 | 200 | 300 | 400 | 500 | あ |
| Measure range(Ip AC) | 0–100 | 0–200 | 0–400 | 0–600 | 0–800 | 0–1000 | あ |
| Rated output(Vo DC) | @Ip=±Ipn AC 5±1% | V | |||||
| Supply voltage | ±12,±15 | V | |||||
| Power Consumption | 25 | mA | |||||
| Offset voltage | @Ip=0 ±30 | mV | |||||
| Offset drift | @ -40~+85℃ ≤±1 | mV /℃ | |||||
| Output drift | @ -40~+85℃ ≤±1 | mA /℃ | |||||
| Linearity | @Ip=0-±Ipn ≤1 | %FS | |||||
| Response time | ≤200 | ms | |||||
| Galvanic isolation | @ 50HZ,AC,1min 2.5 | KV | |||||
| Bandwidth | 40~20000 | HZ | |||||
| Applications |
·Variable speed drives
·Welding machine
·Battery supplied applications
·Uninterruptible Power Supplies (UPS)
·Electrochemical
| Mechanical dimension(for reference only) |

Remarks:
1. All dimensions are in mm.
2. General tolerance ±1mm.
3. Elucidation: 1:+15V 2: -15V 3:V0UT 4:0V
| Standards |
·UL94-V0.
·EN60947-1:2004
·IEC60950-1:2001
·EN50178:1998
·SJ 20790-2000
| General date |
| Value | Unit | |
| Operating temperature(TA) | -40 に +85 | ℃ |
| Storage temperature (TS) |
-40 に +125 | ℃ |
| Mass(約) (M) | 70 | g |







