35mm Hole 1000A 3000: 1 Split Core Current Transformer

Modello numero.
ZEMCTK09-2

Insulating Medium
Insulating Paper

Installazione
Active Type

Magnetic Circuit Structure
Single Stage Type

Voltage Transformation Principle
Capacitive Type

Window Size
35mm

Accuracy
0.5 Class

Turns Ratio
3000:1

Massimo. Attuale
1000UN

Sampling Resistor
10ohm

Pacchetto di trasporto
Cartons

Specifica
ISO9001, ISO14001, CE, ROHS, SGS

Marchio
zeming

Origine
Nanjing, Jiangsu

Codice HS
8504311000

Capacità produttiva
100000PZ/Mese

Descrizione

ZEMCTK09-2 Split core current transformer
Split core current transformer
Mainly used for the Reconstruction project of the distribution system , not power-off stitches, can be quickly loading and unloading.

1.Specifica

Characteristics Values
Primary current 500UN
Maximum primary operating current 1000UN
Secondary current 166.67mA
Sampling resistor 10Ω
Operating frequency 50/60Hz
Temperatura operativa -40ºC-85ºC
Umidità relativa ≤95%
Turn ratio 1:3000
Accurate operating current range 5%Ip~Imax
Accurate class 0.5
Power-frequency Withstand voltage 3kV/1min
Resistenza di isolamento ≥500MΩ/500VDC
Interturn Insulation 500A/1min

Accuracy Class With the percentage(%) of Ip
5 20 100 120
Ratio Error(±%) 3.0 1.5 1.0 1.0
Phase Displacement(±’) 180 90 60 60

2.Dimensione

35mm Hole 1000A 3000: 1 Split Core Current Transformer

3.Material List

NO. Materiale Spec, model UL code SGS
1 Silicon steel core /
2 Core box PBT E332375
3 Nastro Flame retardant,
Environmental protection
E165111
4 Enameled wire 3000turns E258243
5 Outer covering Environmental protection E238981
6 Leading wires Rosso, white, 22#AVR E315651

35mm Hole 1000A 3000: 1 Split Core Current Transformer