Juxta AC Var Transducers

N º de Modelo.
248963-540-AHF-0-METRO

personalizado
personalizado

Marca comercial
jinhan

Origen
China

Código hs
9030339000

Capacidad de producción
5000

Descripción

JUXTA AC VAR TRANSDUCERS

1.GENERAL
The 2469 y 2489 AC VAR transducers produce an analog output equal to the VARS measured by the
input. The typical calibration is 500 VARS / element for 120V and 5A AC transformer secondary inputs.

2.SPECIFICATIONS:

Modelo # 2469 2489
Current input / range 0-1 Amp AC or 0-5 Amp AC
10 para 200% of rated input 0-200% of rated input
Current input over range capability 200% of rated input continuous
1000% of rated input for 5 segundos
Current input burden < 0.2VA per element
Voltage inputs and range: Input powered range
Auxiliary powered range
Voltage input burden per element
120V 240V
100-135VACACIONES 200-264VACACIONES
0-120% rated input
< 0.5voluntad < 1.0voluntad
120V 240V
85-135VACACIONES 170-264VACACIONES
0-120% of rated input
< 0.3voluntad < 0.6voluntad
Sustained Voltage input overange 150% of rated input without damage (Auxiliary powered only)
Rated outputs 0 para ±1mADC into a 10kW max. load; 10VDC output compliance
12±8mADC into a 750W max. load; 15VDC output compliance
Accuracy 0 ± 1mADC = ±0.5% de full scale
12±8mADC = ±0.5% de span
0±1mADC = ±0.1% rdg. ± 0.1%FS
12±8mADC = ±0.2% of span
Output calibration / element 120VACACIONES: 1 Amp = 0-100 VARS; 5 Amp = 0-500 VARS
240VACACIONES: 1 Amp = 0-200 VARS; 5 Amp = 0-1000 VARS
External calibration adjustment Zero: ± 1% minimum
Span: ± 2% minimum
Zero: ± 5% minimum
Span: ± 10% minimum
Tiempo de respuesta < 400 milliseconds (0-99% of output)
Output ripple 0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max.
Isolation 2500 VAC input to output, power and case 2000 VAC aux. power to output and case
500 VAC output to case
Surge Withstand Capability IEEE472/ANSI C37.90.1 – 1989, JIS C1111 (5KV 1.2 X 50 microseconds)
Resistencia de aislamiento > 10 megohm / 500VDC input/output/power/case
Temperatura de funcionamiento -20°C to +60°C
Humedad operativa 0 – 90% relative humidity (non-condensing)
Temperature effect ±250 PPM / °C of span 1mA ±50FS, 4-20mA ±80span (PPM/°C)
External magnetic field < 0.2% at 400 AT/m
Influence : unbalanced currents /
phase interaction / Fuerza Factor
<0.5% <0.2%
Peso 1200gramo (2.65 lbs.)
Choque <0.2% after 50G, 3 Axis and 6 repetitions
Vibración <0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis
UL Recognition File # E60579

3) STANDARD MODELS

120 VACACIONES, 5AAC, 60 Hz, input powered 2469 (0.5% Accuracy) 2489 (0.2% Accuracy)
VAR 1P2W, ±1mA output (1 Elemento)
VAR 1P2W, 12±8mA output (1 Elemento)
VAR 3P3W, ±1mA output (2 Elemento)
VAR 3P3W, 12±8mA output (2 Elemento)
VAR 3P4W, ±1metroA output (212 Elemento)
VAR 3P4W, 12±8metroA output (212 Elemento)
VAR 3P4W, ±1mA output (3 Elemento)
VAR 3P4W, 12±8mA output (3 Elemento)
246961-540-AFB-0-METRO 248961-540-AFB-0-METRO
246961-540-AHF-0-METRO 248961-540-AHF-0-METRO
246963-540-AFB-0-METRO 248963-540-AFB-0-METRO
246963-540-AHF-0-METRO 248963-540-AHF-0-METRO
246964-540-AFB-0-METRO 248964-540-AFB-0-METRO
246964-540-AHF-0-METRO 248964-540-AHF-0-METRO
246965-540-AFB-0-METRO 248965-540-AFB-0-METRO
246965-540-AHF-0-METRO 248965-540-AHF-0-METRO

NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
Auxiliary power supply options <5.0 VA burden.