Descripción
ISOLATOR SWITCH
The isolation switch is the high voltage switch equipment of single phase AC 50Hz. The product is suitable for power system switch on/off when system has voltage but no load.
The isolation switch adopts isolation hook rod to operate.
The isolation switch is the high voltage switch equipment of single phase AC 50Hz. The product is suitable for power system switch on/off when system has voltage but no load.
The isolation switch adopts isolation hook rod to operate.
Solicitud:
- The altitude shall be not more than 1000m
- The ambient temperature: -30degC ~+40degC ; Paramos: -40degC
- Wind pressue: <=700Pa (equals to 34m/s)
- Earthquake strength <=8degree
- Working place with no frequent vibration
- The installation site of ordinary type isolation switch should be kept away from gas, smoke, chemical deposition , salt-spray fog, dust and other explosive and corrosive items that seriously affect insulation and conductivity capacity of the isolator. The pollution-proof type isolator can be installed on the above polluted area but should be avoided from fire and explosion.

| Escribe |
Clasificado Voltaje (kV) |
Clasificado current (A) |
Limit current(kA) |
10sThermally stable current (kA) |
|
| Value Peak | Effective value RMS | ||||
| (H)GW9-12G/200 | 12 | 200 | 5 | 9 | 5 |
| (H)GW9-12G/400 | 12 | 400 | 21 | 15 | 10 |
| (H)GW9-12G/630 | 12 | 630 | 35 | 25 | 14 |
| (H)GW9-12G/800 | 12 | 800 | 55 | 35 | 20 |
| (H)GW9-12G/1000 | 12 | 1000 | 80 | 45 | 28 |
| (H)GW9-12G/1250 | 12 | 1250 | 120 | 55 | 39 |
| (H)GW9-10/200A | 10 | 200 | 5 | 9 | 5 |
| (H)GW9-10/400A | 10 | 400 | 21 | 15 | 10 |
| (H)GW9-10/630A | 10 | 630 | 35 | 25 | 14 |
| (H)GW9-10/800A | 10 | 800 | 55 | 35 | 20 |
| (H)GW9-10/1000A | 10 | 1000 | 80 | 45 | 28 |
| (H)GW9-10/1250A | 10 | 1250 | 120 | 55 | 39
|

| Escribe |
Clasificado Voltaje (kV) |
Clasificado current (A) |
Limit current(kA) |
10sThermally stable current (kA) |
|
| Value Peak | Effective value RMS | ||||
| GWDCD1 | 12 | 630(1250) | 5 | 9 | 5 |
| GWDCD2 | 12 | 630(1250) | 21 | 15 | 10 |
RH-B series outdoor high voltage isolate switch
| Escribe |
Clasificado Voltaje (kV) |
Clasificado current (A) |
4S heat steady e.c (A) | Short current (A) |
Impulse withstand voltage(kV) | Power-frenquency withstand voltage (kV) |
| RH-B | 11 | 400 | 12500 | 31500 | 95 | 42 |
| RH-B | 33 | 600 | 12500 | 31500 | 180 | 80 |