Juxta Frequency Transducers

Αριθμός Μοντέλου.
248982-320-AHD-0

Προσαρμοσμένο
Προσαρμοσμένο

Εμπορικό σήμα
jinhan

Προέλευση
Κίνα

Κωδικός HS
9030339000

Παραγωγική ικανότητα
5000

Περιγραφή

JUXTA COMBINATION WATT/VAR TRANSDUCERS

1.GENERAL
The 2469 και 2489 Frequency transducers have an analog output corresponding to the frequency του the AC input voltage. These transducers are capable του high accuracy measurement over various frequency ranges.

2.SPECIFICATIONS:

Μοντέλο # 2469 2489
Voltage inputs and range:
Input powered range Auxiliary powered range
Voltage input burden
120V: 100 – 135 VAC, 240V: 200 – 264 VAC
±20% of rated voltage 120VAC <0.1 VA; 240VAC <0.2 VA
Rated outputs ±1mADC into a 10kWmax. load; 10VDC output compliance
4-12-20 mADC into 750W max. load; 15VDC output compliance
Accuracy: ±2, 5, 10, 25 Hz deviation
±0.5, 1 Hz deviation
±1% of input span
±2% of input span
0-1mADC=±0.1% of input span 0-1mADC=±0.2% of input span
4-20mADC=add±0.1% to accuracy
External calibration adjustment Zero: ±1% minimum
Span: ±2% minimum
Zero: ±5% minimum
Span: ±10% minimum
Response time <400 milliseconds (0-99% of output)
Output ripple 0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max.
Isolation 2500 VAC input to output, power and case 2000 VAC aux. power to output and case
500 VAC output to case
Surge Withstand Capability IEEE472/ANSI C37.90.1 1989, JIS C1111(5KV 1.2 x 50 microseconds)
Αντοχή μόνωσης >10 megohm / 500VDC input/output/power/case
Θερμοκρασία λειτουργίας -20°C to +60°C
Operating humidity 0 – 90% relative humidity (non-condensing)
Temp. effect: ±2, 5, 10, 25 Hz deviation
±0.5, 1 Hz deviation
± 250 PPM / °C of span
± 500 PPM / °C of span
±25ppm of center frequency(60Hz±5Hz)
±5ppm of center frequency(60Hz±0.5Hz) For 4-20mADC multiply ppm x 1.4
External magnetic field < 0.2% at 400 AT/m
Harmonics Fundamental through 9th harmonic
Βάρος 1000σολ (2.2 lbs.)
Shock < 0.2% after 50G, 3 Axis and 6 repetitions
Vibration < 0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3Axis
UL Recognition File # E60579

3) STANDARD MODELS:

120VAC, 60 Hz, input powered 2469 2489
Freq. ± 1.0 Hz deviation, 0-1mA output
Freq. ± 1.0 Hz deviation, 4-20mA output
Freq. ± 2.0 Hz deviation, 0-1mA output
Freq. ± 2.0 Hz deviation, 4-20mA output
Freq. ± 5.0 Hz deviation, 0-1mA output
Freq. ± 5.0 Hz deviation, 4-20mA output
246982-320-AFA-0
246982-320-AHD-0
246983-320-AFA-0
246983-320-AHD-0
246984-320-AFA-0
246984-320-AHD-0
248982-320-AFA-0
248982-320-AHD-0
248983-320-AFA-0
248983-320-AHD-0
248984-320-AFA-0
248984-320-AHD-0

NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
Auxiliary power supply options <5.0 VA burden.