Juxta AC Var Transducers

Modell Nr.
248963-540-AHF-0-M

Angepasst
Angepasst

Warenzeichen
jinhan

Herkunft
China

HS-Code
9030339000

Produktionskapazität
5000

Beschreibung

JUXTA AC VAR TRANSDUCERS

1.GENERAL
Der 2469 und 2489 AC VAR transducers produce an analog output equal to the VARS measured by the
input. The typical calibration is 500 VARS / element for 120V and 5A AC transformer secondary inputs.

2.SPECIFICATIONS:

Modell # 2469 2489
Current input / range 0-1 Amp AC or 0-5 Amp AC
10 Zu 200% of rated input 0-200% of rated input
Current input over range capability 200% of rated input continuous
1000% of rated input for 5 Sekunden
Current input burden < 0.2VA per element
Voltage inputs and range: Input powered range
Auxiliary powered range
Voltage input burden per element
120v 240v
100-135VAC 200-264VAC
0-120% rated input
< 0.5VA < 1.0VA
120v 240v
85-135VAC 170-264VAC
0-120% of rated input
< 0.3VA < 0.6VA
Sustained Voltage input overange 150% of rated input without damage (Auxiliary powered only)
Rated outputs 0 Zu ±1mADC into A 10kW max. load; 10VDC output compliance
12±8mADC into a 750W max. load; 15VDC output compliance
Accuracy 0 ± 1mADC = ±0,5 % von full scale
12±8mADC = ±0,5 % von span
0±1mADC = ±0.1% rdg. ± 0.1%FS
12±8mADC = ±0.2% of span
Output calibration / element 120VAC: 1 Amp = 0-100 VARS; 5 Amp = 0-500 VARS
240VAC: 1 Amp = 0-200 VARS; 5 Amp = 0-1000 VARS
External calibration adjustment Zero: ± 1% minimum
Span: ± 2% minimum
Zero: ± 5% minimum
Span: ± 10% minimum
Ansprechzeit < 400 milliseconds (0-99% of output)
Output ripple 0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max.
Isolation 2500 VAC input to output, power and case 2000 VAC aux. power to output and case
500 VAC output to case
Surge Withstand Capability IEEE472/ANSI C37.90.1 – 1989, JIS C1111 (5KV 1.2 X 50 microseconds)
Isolationswiderstand > 10 megohm / 500VDC input/output/power/case
Betriebstemperatur -20°C to +60°C
Operating humidity 0 – 90% relative humidity (non-condensing)
Temperature effect ±250 PPM / °C of span 1mA ±50FS, 4-20mA ±80span (PPM/°C)
External magnetic field < 0.2% bei 400 AT/m
Influence : unbalanced currents /
phase interaction / Leistung Factor
<0.5% <0.2%
Gewicht 1200g (2.65 lbs.)
Shock <0.2% after 50G, 3 Axis and 6 repetitions
Vibration <0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis
UL Recognition File # E60579

3) STANDARD MODELS

120 VAC, 5AAC, 60 Hz, input powered 2469 (0.5% Accuracy) 2489 (0.2% Accuracy)
VAR 1P2W, ±1mA output (1 Element)
VAR 1P2W, 12±8mA output (1 Element)
VAR 3P3W, ±1mA output (2 Element)
VAR 3P3W, 12±8mA output (2 Element)
vEINR 3P4W, ±1mEIN outpuT (212 Element)
vEINR 3P4W, 12±8mEIN outpuT (212 Element)
VAR 3P4W, ±1mA output (3 Element)
VAR 3P4W, 12±8mA output (3 Element)
246961-540-AFB-0-M 248961-540-AFB-0-M
246961-540-AHF-0-M 248961-540-AHF-0-M
246963-540-AFB-0-M 248963-540-AFB-0-M
246963-540-AHF-0-M 248963-540-AHF-0-M
246964-540-AFB-0-M 248964-540-AFB-0-M
246964-540-AHF-0-M 248964-540-AHF-0-M
246965-540-AFB-0-M 248965-540-AFB-0-M
246965-540-AHF-0-M 248965-540-AHF-0-M

NOTIZ: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
Auxiliary power supply options <5.0 VA burden.